Air-cooled chiller

Evaporator types and selection

Plate, shell-and-tube or flooded? We explain how each evaporator type works, where it is used and what to look for when choosing.

In shortAn evaporator is a heat exchanger in which the refrigerant evaporates and absorbs heat from water or air. In chillers the most common types are brazed plate, shell-and-tube (DX), flooded and falling film; in air conditioners and cold rooms, finned coils (air coolers) are used. The right type is chosen according to capacity, refrigerant, water quality, freezing risk and cleanability.

What is an evaporator and what does it do?

The four main components of the refrigeration cycle are the compressor, condenser, expansion valve and evaporator. The refrigerant leaving the expansion valve at low pressure and temperature evaporates in the evaporator, absorbing heat from the water (chiller) or air (air conditioner, cold room). The evaporator is one of the surfaces that determines the cooling capacity of the system. Fouling, freezing or disrupted flow directly affects capacity and compressor health.

Evaporator types

TypeHow it worksTypical useService note
Brazed plateThin stainless steel plates joined by brazing; the refrigerant and water pass through alternating channelsAir-cooled chillers with scroll compressors, heat pumps, small and medium capacityCompact and efficient; cannot be disassembled. Sensitive to fouling and freezing, a strainer is essential upstream of the water
Shell-and-tube, direct expansion (DX)The refrigerant usually evaporates inside the tubes and the water flows on the shell side between baffle plates (it may be the reverse depending on the manufacturer)Medium and large capacity screw and scroll chillersOil return is good; the tube side can be cleaned, while the shell side is mostly cleaned chemically
Flooded shell-and-tubeThe refrigerant floods the tubes in the shell, and the water passes through the inside of the tubesLarge screw and centrifugal chillersHigh efficiency; the water side can be cleaned mechanically with a brush. The refrigerant charge is larger, and oil management is a separate circuit
Falling filmThe refrigerant is distributed over the tubes as a thin film, and the water is inside the tubesLarge screw and centrifugal chillersLower refrigerant charge and high efficiency; the distribution system is sensitive and requires manufacturer information
Double-pipe (coaxial)One pipe inside another; the two fluids flow in opposite directionsSmall water-cooled packaged units and heat pumpsCompact at small capacities; scale and freezing can cause hidden damage in the inner pipe
Finned coil (DX)Copper tubes and aluminum fins; the air is cooled as it passes over the finsSplit and VRF indoor units, ducted air conditioners, rooftop unitsFilter and fin fouling reduces capacity; the drain pan must be clean
Air cooler (unit cooler)Finned coil, fan and defrost system in one housingCold rooms, freezers, process coolingDefrost type and fin spacing are chosen according to room temperature

Defrost methods for cold room air coolers

  • Electric heater defrost: the most common method
  • Hot gas defrost: used in large systems, and is fast
  • Air (natural) defrost: for applications where the room temperature is above zero
  • Defrost sensor, duration and termination settings: a wrong setting leads to ice buildup or unnecessary heating

Direct expansion or flooded?

FeatureDirect expansion (DX)Flooded
Refrigerant chargeLowerHigher
EfficiencyGoodGenerally higher; the temperature difference between the refrigerant and the water is small
Oil returnGenerally easyRequires an oil recovery circuit
Capacity rangeSmall and mediumMedium and large
CleaningWater side mostly chemicalMechanical brushing inside the tubes is possible

What to look for when choosing an evaporator

CriterionWhy it matters
Capacity and water temperatures (7/12 °C, low temperature with glycol)Selection is based on actual operating conditions, not nominal capacity
Refrigerant (R134a, R410A, R32, R513A, R1234ze, etc.)Pressure class, material and oil compatibility depend on the refrigerant
Water quality and filtrationScale, sludge and chlorides cause clogging and corrosion in plates and tubes
Water-side pressure dropAffects pump selection and flow balance
Freeze protectionGlycol ratio, flow switch and low-temperature protection are part of the design
Material (stainless steel plate, copper or steel tubes, steel shell)Corrosion resistance and service life are determined by this
CleanabilityTypes that can be cleaned mechanically are advantageous with dirty water
Insulation, layout and service accessSweating and ease of maintenance
Pressure class and certificates (CE/PED)Pressure vessel safety

For flow, glycol and heat exchangers, you can use the chiller flow calculator, glycol freezing point and heat exchanger LMTD calculators for preliminary calculations.

Why is evaporator freezing dangerous?

When water freezes, its volume increase cracks the plates or tubes; a crack lets water and refrigerant mix. The most common causes are low water flow, a dirty strainer, a bypassed flow switch, a setpoint that is too low, an insufficient glycol ratio and low load.

  • The flow switch or differential pressure switch must be in the circuit
  • The glycol ratio must be measured and checked according to the season
  • Low-temperature and low-pressure protections must be tested
  • The strainer must be cleaned regularly
  • There must be an operating interlock between the pump and the chiller

For glycol and winter preparation, see our chiller winter preparation article.

What is done in evaporator maintenance?

  • Water-side strainer cleaning
  • Water quality and glycol check
  • Recording approach temperature, superheat and water ΔT
  • Water-side pressure drop and flow check
  • Insulation and sweating check
  • Coil fin and drain pan cleaning
  • Defrost parts and sensor check (cold room)
  • Pressure test when a cross-leak is suspected

For fault symptoms, repair options and replacement, see our evaporator repair and replacement page; for periodic maintenance, see chiller maintenance.

Note: This page is for general technical information. For a unit-specific decision, the manufacturer's manual and on-site measurement apply. YOİ Mühendislik is an independent technical service for these brands; it does not claim to be an authorized service except for LG.

Facilities we serve

ChillerCold roomProcess coolingRooftop unitVRFIndustrial facility

Our headquarters is in Etimesgut, Ankara. We provide this service daily in Ankara, and on a project and contract basis in all 81 provinces of Türkiye, including İstanbul, İzmir, Bursa, Antalya, Konya, Kayseri, Eskişehir, Kocaeli, Adana, Gaziantep, Samsun and Trabzon. See the areas we serve.

Frequently asked questions

Which is better, a plate or a shell-and-tube evaporator?

Neither is absolutely superior. The plate type is compact and efficient but cannot be disassembled and is sensitive to dirty water. The shell-and-tube type is more tolerant, and on the flooded type in particular the inside of the tubes can be cleaned mechanically. The choice is made based on capacity, water quality and ease of service.

What is the difference between an evaporator and a condenser?

In the evaporator the refrigerant absorbs heat by evaporating; in the condenser it rejects heat by condensing. Both are heat exchangers; their operating pressures and temperatures differ.

What happens if evaporator capacity drops?

The chilled water outlet temperature rises and the compressor runs for a long time; low-pressure or freeze alarms may appear.

How long does an evaporator last?

It depends on water quality, filtration, freezing incidents and the maintenance routine; giving a fixed period would not be accurate.

Which refrigerants are used?

Refrigerants such as R134a, R410A, R32, R513A and R1234ze, according to the refrigerant on the unit nameplate. A change of refrigerant also affects evaporator selection.

Do you provide evaporator service for every brand?

As an independent technical service, we carry out diagnosis, repair, and equivalent evaporator selection and replacement for all brands. Lead time and parts availability are stated in writing in the quote.

Let's decide by measuring.

Diagnosis, a written report, and a quote that lists repair and replacement costs side by side. For all brands and equipment, across Türkiye.

Bize ulaşın

Teklif alın, aynı gün dönüş yapalım

Cihazınızı ve ihtiyacınızı kısaca yazın; ilgili mühendisimiz sizi arasın. Arıza, bakım, sözleşme veya yeni cihaz için tek adres.

Yetkili ServisTSE Hizmet Yeterlilik Belgesi2009'dan beri

Hızlı teklif formu

Form WhatsApp mesajı olarak iletilir.

Detaylı talep için teklif formunu kullanabilirsiniz.