Air-cooled chiller

Evaporator repair and replacement

Before replacing the evaporator, we tell you by measurement whether it can be repaired. We write the repair and replacement costs side by side in the quote.

In shortAn evaporator fault usually appears as reduced capacity, a freeze alarm, increased water-side pressure drop, or water mixing with the refrigerant. Fouling can be removed by chemical or mechanical cleaning; a frozen brazed plate evaporator, however, usually cannot be repaired and is replaced. The decision is based on measurement; replacing it without eliminating the root cause of the damage puts the new evaporator at risk too.

Scope of service

  • Evaporator fault diagnosis and written report
  • Water-side chemical cleaning and backflushing
  • Tube brushing, plugging and replacement in shell-and-tube evaporators
  • Brazed plate evaporator replacement
  • Cross-leak (water-gas) pressure test
  • Air cooler and coil cleaning, defrost parts
  • Expansion valve, filter drier and oil check
  • Commissioning, performance measurement and report

Evaporator fault symptoms

SymptomLikely causeWhat is done
Chilled water outlet temperature rises, compressor runs for a long timeScale or sludge on the water side, oil buildup, low refrigerantMeasure approach temperature and superheat; chemical cleaning or refrigerant check
Freeze alarm, low-pressure tripLow water flow, dirty strainer, low setpoint temperature, insufficient glycolCheck flow and strainer, measure glycol, check protection settings
Water-side pressure drop is increasingPlate channels or tubes are cloggingBackflushing, chemical cleaning
Bubbles in the expansion tank, water pressure fluctuatingLeak from the refrigerant side into the water (tube or plate crack)Pressure test and locating the leak
Moisture and acid in the refrigerant circuit, filter drier saturates quicklyWater leaking into the refrigerant circuitLeak detection, repair or replacement, system dehydration and cleaning
Oil return problem, low oil in the compressorOil buildup in the evaporator, insufficient refrigerant velocityCheck oil return, clean if necessary
Excessive ice on the air coolerDefrost fault, blocked fins, fan faultCheck defrost element, sensor, drain pan heater and fan
Water overflowing from the drain pan, odorClogged drain, dirty panCleaning, drain slope and disinfection

How is an evaporator fault diagnosed?

  1. Data and alarm history. Operating hours, alarm records, current, pressures and temperatures are recorded.
  2. Thermodynamic measurement. Approach temperature, superheat and water inlet and outlet temperatures (ΔT) are measured.
  3. Water-side measurement. Flow and water-side pressure drop are checked; the strainer and water quality are inspected.
  4. Cross-leak test. The refrigerant is recovered, one side is pressurized with nitrogen and the pressure on the other side is monitored.
  5. Written report. Measurement values, the recommended action, and the repair and replacement costs are written as separate items.

Repair options

MethodWhenNote
Chemical cleaning (CIP)Scale, sludge, foulingThe chemical is chosen according to the evaporator material; neutralization and rinsing are carried out
Mechanical cleaning (brushing)Inside the tubes on flooded and shell-and-tube typesCannot be applied to brazed plate types
Tube pluggingIf a few tubes leak on a shell-and-tube typeCapacity drops somewhat; as the number of tubes grows, replacement becomes the better option
Tube replacement / retubingWidespread tube damage on shell-and-tube typesBased on manufacturer dimensions and tube material
Brazing or welding repairLeaks at connections and copper pipesVerified by a pressure test
Coil washing and fin combingAir cooler, indoor unitBent and blocked fins are corrected
Defrost and sensor partsCold room air coolerHeating element, sensor, solenoid, drain pan heater
Insulation renewalSweating and heat lossVapor barrier continuity is important

When is evaporator replacement needed?

SituationRecommendation
Frozen and cracked brazed plate evaporatorUsually replacement; a brazed joint cannot be repaired
Leaks in many tubes or widespread corrosion (shell-and-tube)Replacement or retubing, depending on measurement
Repeated clogging, capacity not restored by cleaningReplacement; should be considered together with water treatment
Refrigerant change or capacity increaseAn evaporator suited to the new pressure class and capacity
The manufacturer's model is discontinued and parts cannot be foundEquivalent evaporator
The root cause of the damage has not been eliminatedThe cause is fixed first; otherwise the new evaporator will be damaged too

What is checked when choosing an equivalent evaporator

CheckWhy it matters
Capacity and water temperaturesCapacity is verified under actual operating conditions
Refrigerant and pressure classMaterial and strength suited to the refrigerant
Water and refrigerant connection type and dimensionsRisk of pipe changes and extra cost
Number of circuits and expansion valve compatibilitySuperheat control and capacity staging
Water-side pressure dropThe pump and flow balance should not be disturbed
Plate and shell materialResistance to water quality
Insulation and layoutInstallation and service access

What is done after replacement

  • Vacuum and nitrogen pressure test
  • Oil and filter drier replacement (if needed)
  • Strainer cleaning or renewal
  • Expansion valve and superheat adjustment
  • Glycol ratio and freeze protection check
  • Flow switch and low-temperature protection test
  • Performance measurement and records
  • Written report

How does an evaporator replacement proceed?

  1. Diagnosis and report. It is verified by measurement that the fault comes from the evaporator.
  2. Quote. Repair and replacement options are written side by side with their cost items.
  3. Supply and preparation. An equivalent evaporator is supplied; shutdown and refrigerant recovery are planned.
  4. Removal and installation. The water side is drained, the old evaporator is removed, and the new one is connected and insulated.
  5. Testing and charging. Pressure test, vacuum, oil and refrigerant charging are carried out.
  6. Commissioning. Protection settings are tested, performance is measured and a report is provided.

So the same damage does not recur

A significant share of evaporator damage is system-related: reduced flow from a closed valve or dirty strainer, a bypassed protection, a setpoint that is too low, insufficient glycol, or uncontrolled water quality. For this reason, along with the replacement we carry out a root cause analysis and test the protection settings. For compressor-side consequences see our compressor overhaul page, and for the refrigerant side see refrigerant leaks and refrigerant charging.

Note: This page is for general technical information. For a unit-specific decision, the manufacturer's manual and on-site measurement apply. YOİ Mühendislik is an independent technical service for these brands; it does not claim to be an authorized service except for LG.

Facilities we serve

ChillerCold roomProcess coolingRooftop unitVRFIndustrial facility

Our headquarters is in Etimesgut, Ankara. We provide this service daily in Ankara, and on a project and contract basis in all 81 provinces of Türkiye, including İstanbul, İzmir, Bursa, Antalya, Konya, Kayseri, Eskişehir, Kocaeli, Adana, Gaziantep, Samsun and Trabzon. See the areas we serve.

Frequently asked questions

Can a brazed plate evaporator be repaired?

Generally no. A brazed joint cannot be disassembled and a cracked plate cannot be repaired, so replacement is needed. Fouling, however, can be removed by chemical cleaning.

What should I do if the evaporator freezes?

Do not restart the unit and call for service. Water and refrigerant may be mixing through a cracked plate; restarting can increase compressor damage.

How can I tell if refrigerant is leaking into the water?

Bubbles in the expansion tank, fluctuating water pressure, and oil or odor in a water analysis can be signs. A definitive diagnosis is made with a pressure test.

How long does evaporator replacement take?

It depends on the unit and the evaporator's lead time; the duration is stated in writing in the quote.

Why does ice form on a cold room air cooler?

The most common causes are a defrost element or sensor fault, incorrect defrost duration, a fan fault or blocked fins.

Do you work on every brand?

As an independent technical service, we work on all brands. Parts and equivalent evaporator supply are stated in writing in the quote according to the unit.

Let's decide by measuring.

Diagnosis, a written report, and a quote that lists repair and replacement costs side by side. For all brands and equipment, across Türkiye.

Bize ulaşın

Teklif alın, aynı gün dönüş yapalım

Cihazınızı ve ihtiyacınızı kısaca yazın; ilgili mühendisimiz sizi arasın. Arıza, bakım, sözleşme veya yeni cihaz için tek adres.

Yetkili ServisTSE Hizmet Yeterlilik Belgesi2009'dan beri

Hızlı teklif formu

Form WhatsApp mesajı olarak iletilir.

Detaylı talep için teklif formunu kullanabilirsiniz.