Air conditioner and VRF fault codes
The meaning, likely cause and what you can do for 204 error codes across 8 brands. Search for the code, choose the brand.
LG fault codes
| Code | Meaning | Likely cause | What can you do? |
|---|---|---|---|
| CH01 | Indoor unit room (air intake) temperature sensor fault | Sensor open/short circuit, loose connector or indoor unit board fault | Do a safe reset (breaker off for ~5 min). If the code returns, service is needed. |
| CH02 | Indoor unit pipe inlet temperature sensor fault | Sensor open/short circuit or connection problem | Do a safe reset. If the code returns, service is needed. |
| CH03 | Communication error between the wired controller and the indoor unit | Indoor unit board is not receiving the controller signal; controller cable or board problem | Do a safe reset. If it continues, service is needed. |
| CH04 | Drain (condensate discharge) error | Drain pump/float problem or blocked discharge on ceiling-type units; full water tank on portable/window types. On some models it appears as FL. | On portable/window types, empty the water through the drain plug described by the manufacturer. On ceiling/cassette types do a reset; if it continues, service is needed. |
| CH05 / CH53 / E0 | Communication error between the indoor and outdoor unit | Faulty/loose communication cable connection, wiring error after installation or relocation, mains fluctuation, board fault. On some models 'E0' may appear on the display while kW Manager is running (this is not a fault). | Do a safe reset. If the error appeared after a new installation or relocation, contact the installer; if it continues, service is needed. |
| CH06 | Indoor unit pipe outlet temperature sensor fault | Sensor open/short circuit or connection problem | Do a safe reset. If the code returns, service is needed. |
| CH07 | Indoor units are in different operating modes (mode conflict) | In multi split / 2-in-1 systems one unit is heating while the other is cooling or dehumidifying | Set all indoor units to the same mode (all heating, or all cooling/dehumidifying). Fan and air-purifying modes can be used without restriction. |
| CH09 | Indoor unit EEPROM (memory) error | Faulty memory data on the indoor unit board or board fault | Service required |
| CH10 / E6 | Indoor unit fan motor fault | Fan motor connector came off, motor is locked, or there is an obstruction in front of the fan | Without opening the unit, remove any visible obstruction at the indoor unit air inlet/outlet and do a reset. If it continues, service is needed. |
| CH12 | Sensor-related error (listed among the sensor group codes in LG's official source) | Faulty/loose sensor, board error or temporary electrical problem. Which sensor it is can vary by series. | Do a safe reset. If the code returns, service is needed. |
| CH21 | Inverter compressor driver (IPM/IGBT) error – DC peak | Power module protection tripped; compressor, driver board or sudden voltage problem | Do a safe reset. If the code returns, service is needed. |
| CH22 | Inverter board input overcurrent (Max CT) | Outdoor unit inverter board input current exceeded the limit | Service required |
| CH23 | Compressor DC link low voltage error | DC voltage is not produced after the outdoor unit starts; supply or board problem | Do a safe reset. If it continues, service is needed. |
| CH24 | Outdoor unit high pressure switch tripped (Multi V) | High pressure, dirty condenser or insufficient air/water flow | Remove any items around the outdoor unit that block airflow. Service is required. |
| CH25 | Outdoor unit input voltage too high or too low | Mains voltage is outside limits | Watch whether there are voltage fluctuations across the building, and do a reset. If it continues, service is needed. |
| CH26 | Inverter compressor initial start error | Compressor or driver circuit fault (some sources list it as a compressor position detection error) | Do a safe reset. If it continues, service is needed. |
| CH29 | Inverter compressor overcurrent error | Compressor or power element (IGBT) fault, phase problem | Do a safe reset. If it continues, service is needed. |
| CH32 | Excessive rise in inverter compressor discharge temperature | Insufficient refrigerant, flow problem or sensor problem | Service required |
| CH34 | Excessive rise in high pressure | Dirty condenser, insufficient outdoor unit ventilation, overcharge of gas. On some models it is also shown for overheating in heating mode. | Clear the area around the outdoor unit and clean the indoor unit filter. If it continues, service is needed. |
| CH38 / F4 | Refrigerant (gas) shortage protection | Gas leak, insufficient charge or pipe connection problem | If it appeared after installation/relocation, contact the installer. If it appeared during normal use, do one reset; if it repeats, service is needed. |
| CH41–CH48 | Outdoor unit sensor errors (discharge, pressure, outdoor air, condenser, suction line, etc.) | Sensor fault/loose connection or board error. Which number is which sensor can vary by series. | Do a safe reset. If the code returns, service is needed. |
| CH54 | Reverse phase / phase sequence error | Usually the phase sequence of the three-phase supply changing after a power outage or electrical work | Switch the air conditioner's breaker off and on. If it appeared after electrical work, tell the electrician it is a 'reverse phase' error; if it continues, service is needed. |
| CH61 | Outdoor unit overheating in cooling / indoor unit overheating in heating | Hot air building up around the outdoor unit (closed balcony, closed louver, stacked items) or a dirty/blocked filter in heating. On some models it appears as P4, P6, P7, P8 or CH34. | Clear the front and surroundings of the outdoor unit, keep the ventilation window/louver open and clean the indoor unit filter. The code does not clear by itself; do a reset. If it continues, service is needed. |
| CH66 | Communication line or pipe connection problem between indoor and outdoor unit | Usually a wrong cable/pipe connection during installation; sometimes a temporary electrical fluctuation | If it appeared after a new installation, contact the installer; otherwise do a reset. If it continues, service is needed. |
| CH67 / EF | Outdoor unit fan motor error (fan lock) | Obstruction in front of the outdoor fan, snow/ice buildup or fan motor fault | From the outside, clear obstructions such as leaves, bags or snow around the outdoor unit. If it continues, service is needed. |
| CH90 / CH91 | Protection during test run (pipe connection/flow problem) | Pipe connection or flow problem after installation; on some models it appears as F4 | If it is after installation, contact the installer. In normal use, do a reset; if it continues, service is needed. |
| CH93 | Indoor-outdoor communication error; on some models after 2021, the outdoor unit is without power | The plug of the separately plugged outdoor unit has come out or its fuse is off, communication cable problem | Check that the outdoor unit's plug is connected directly to a wall socket (do not use a multi-socket strip) and that its fuse is on. If the fuse keeps tripping, do not force it; service is required. |
Source: lg.com · lg.com · manualslib.com
Daikin fault codes
| Code | Meaning | Likely cause | What can you do? |
|---|---|---|---|
| A1 | Indoor unit electronic board (PCB) fault | Indoor unit board error | Do a safe reset. If it continues, service is needed. |
| A3 | Drain level control system error (cassette/duct types, SkyAir/VRV) | Drain pump, float or blocked drain line | Switch the unit off; do not use it if water is dripping from the indoor unit. Service is required. |
| A5 | Freeze protection (in cooling) / high pressure control (in heating) | Dirty filter, blocked air inlet/outlet, low airflow or gas problem | Clean the air filter, make sure nothing blocks the indoor unit's air inlet/outlet, and do a reset. If it continues, service is needed. |
| A6 | Indoor unit fan motor fault | Fan motor locked, connector problem or foreign object caught in the fan | Do a safe reset. If it continues, service is needed. |
| C4 | Indoor unit heat exchanger (coil) temperature sensor fault | Sensor open/short circuit or connection problem | Service required |
| C9 | Indoor unit intake air (room) temperature sensor fault | Sensor open/short circuit or connection problem | Service required |
| E1 | Outdoor unit electronic board fault | Outdoor unit board error or indoor-outdoor relay connection problem | Do a safe reset. If it continues, service is needed. |
| E3 | High pressure switch (HPS) tripped | Dirty outdoor unit heat exchanger, blocked piping, faulty pressure switch | Remove items blocking the outdoor unit's air inlet/outlet. Service is required. |
| E4 | Low pressure switch (LPS) tripped | Abnormal drop in low pressure (could be a gas shortage), sensor/board fault | Service required |
| E5 | Compressor overload (OL) / overheating protection | Inverter compressor lock, high pressure difference, inverter board fault | Service required |
| E6 | Compressor start error / compressor lock | Compressor or control board fault, service valve left closed | Service required |
| E7 | Outdoor unit DC fan motor fault | Fan motor fault, connection problem or foreign object caught in the fan | From the outside, clear obstructions such as leaves, bags or snow in front of the outdoor fan. If it continues, service is needed. |
| E8 | Input overcurrent (inverter compressor overcurrent) | Compressor, inverter capacitor, outdoor board or power transistor fault | Service required |
| F3 | Discharge pipe high temperature protection | Gas shortage, discharge sensor fault or outdoor board problem | Service required |
| F6 | High pressure control (in cooling) / gas overcharge | Excess refrigerant, sensor disconnection, insufficient outdoor unit ventilation | Clear the area around the outdoor unit. If it continues, service is needed. |
| H0 | Compressor sensor system fault | Cable connection broken or board error | Service required |
| H6 | Stop due to position detection sensor error | Compressor rotor position detection circuit fault | Service required |
| H8 | DC current sensor fault | Outdoor unit board/sensor error | Service required |
| H9 | Outdoor air temperature sensor fault | Sensor open/short circuit. Note: the Daikin India table lists H9 as the 'intake air sensor'; in the global Daikin table it is the 'outdoor air thermistor'. It can vary by series. | Service required |
| J3 | Discharge pipe temperature sensor fault | Sensor open/short circuit | Service required |
| L4 | Inverter heat sink temperature high | Insufficient outdoor unit ventilation, outdoor fan fault | Clear the area around the outdoor unit and the air outlet, and remove any direct sun or hot air buildup. If it continues, service is needed. |
| L5 | Inverter output overcurrent (instantaneous) | Compressor winding fault, compressor start problem (mechanical lock), inverter board fault | Service required |
| U0 | Refrigerant (gas) shortage | Gas leak or insufficient charge | Service required |
| U2 | Supply voltage drop or main circuit overvoltage | Mains voltage fluctuation, sudden outage | Do a safe reset after the mains fluctuation has passed. If it continues, service is needed. |
| U4 | Communication error between the indoor and outdoor unit | Communication cable, outdoor unit without power or board problem | Check that the outdoor unit's fuse is on and do a safe reset. If it continues, service is needed. |
| UA | Indoor and outdoor unit combination (mismatch) error | Incompatible indoor/outdoor unit pairing or setting error | Service required |
Source: daikinindia.com · daikin.com · daikin.com
Mitsubishi Electric fault codes
| Code | Meaning | Likely cause | What can you do? |
|---|---|---|---|
| P1 | Intake (room) temperature sensor (TH1) fault | Sensor open/short circuit or connector came off | Service required |
| P2 | Pipe (liquid line, TH2) temperature sensor fault | Sensor open/short circuit or connector came off | Service required |
| P4 | Drain sensor error / float connector open | Drain sensor or float connection problem | Service required |
| P5 | Drain pump error / water overflow protection in the indoor unit | Drain pump fault, blocked drain line or pan | Switch the unit off; do not use it if water is dripping. Service is required. |
| P6 | Freeze (in cooling) / overheating (in heating) protection | Dirty filter or heat exchanger, low airflow, fan motor problem, gas problem | Clean the air filter, clear the indoor unit air inlet/outlet and do a reset. If it continues, service is needed. |
| P8 | Pipe temperature abnormality | No expected temperature change at the indoor unit during operation; gas leak, closed service valve, sensor coming off its position, reversed pipe/cable connection in multi systems | Service required |
| P9 | Pipe (TH5, condenser/evaporator) temperature sensor fault | Sensor open/short circuit or connector came off | Service required |
| PA | Forced compressor stop (due to water leak abnormality) | Drain/water leak detection | Switch the unit off. Service is required. |
| Pb (PB) | Indoor unit fan motor error | Fan motor or driver circuit fault | Service required |
| E0 / E3 | Controller transmission (communication) error | Controller cable, group/master-slave setting or board problem | Do a safe reset. If it continues, service is needed. |
| E1 / E2 | Controller control board error | Wired controller fault | Service required |
| E4 / E5 | Communication error between the wired controller and the indoor unit | Controller signal cannot be received; cable or board problem | Do a safe reset. If it continues, service is needed. |
| E6 / E7 | Communication error between the indoor and outdoor unit | Connection cable, outdoor unit without power or board problem | Check the outdoor unit's fuse and do a safe reset. If it continues, service is needed. |
| E9 | Indoor-outdoor communication error (transmission error on the outdoor unit side) | Communication line or outdoor unit board problem | Service required |
| EE | Indoor and outdoor unit combination/communication error | Incompatible indoor/outdoor unit pairing or connection error | Service required |
| Fb (FB) | Indoor unit control system error (memory error, etc.) | Indoor unit board fault | Service required |
| U1 / Ud | Abnormal high pressure (63H switch) / overheating protection | Outdoor fan fault, blocked/dirty outdoor heat exchanger, blockage in the system; dirty indoor filter in heating. City Multi equivalent: 1302. | Clear the area around the outdoor unit and clean the indoor filter in heating. If it continues, service is needed. |
| U2 | Abnormally high discharge temperature / insufficient refrigerant | Gas shortage, thermistor problem, high ambient temperature. City Multi equivalent: 1102. | Service required |
| U3 / U4 | Open/short circuit in outdoor unit thermistors (discharge, outdoor air, heat exchanger, etc.) | Sensor fault or connector came off. City Multi equivalent: 5104 / 5105. | Service required |
| U5 | Outdoor unit heat sink temperature abnormal | Short circuit of the outdoor unit air outlet (hot air being drawn back in), thermistor problem. City Multi equivalent: 4230. | Clear the front and surroundings of the outdoor unit and prevent hot air buildup. If it continues, service is needed. |
| U6 | Compressor overcurrent cutoff / power module abnormality | Compressor or inverter power module problem. City Multi equivalent: 4250. | Service required |
| U7 | Superheat abnormality due to low discharge temperature | Expansion valve (LEV) or sensor problem. City Multi equivalent: 1520. | Service required |
| U8 | Outdoor unit fan safety stop | Outdoor fan motor fault or obstruction caught in the fan | From the outside, clear obstructions in front of the outdoor fan. If it continues, service is needed. |
| U9 / UH | Over/under voltage, main circuit sync signal error or current sensor error | Mains voltage problem, compressor wiring or board fault | Do a safe reset after the mains fluctuation has passed. If it continues, service is needed. |
| UF / UP | Compressor overcurrent cutoff (UF: compressor lock) | Closed service valve, compressor wiring, compressor fault, outdoor unit air short circuit | Service required |
Source: mitsubishielectric.com.sg · mitsubishi-electric.manymanuals.com · orionair.co.uk
Samsung fault codes
| Code | Meaning | Likely cause | What can you do? |
|---|---|---|---|
| CF | Filter cleaning reminder (not a fault) | Filter usage time has expired | Clean the indoor unit filters and reset the reminder from the remote. |
| dF | Automatic defrost is running in heating (not a fault) | Frost on the outdoor unit heat exchanger is being melted | Wait; the indoor fan may stop briefly, and steam coming from the outdoor unit is normal. |
| E101 / E102 | Communication error between the indoor and outdoor unit | Communication cable connection, outdoor unit without power or board problem | Do a safe reset. If it continues, service is needed. |
| E121 | Indoor unit room temperature sensor error | Sensor open/short circuit | Service required |
| E122 | Indoor unit pipe (evaporator inlet) sensor error | Sensor open/short circuit | Service required |
| E154 | Indoor unit fan motor speed error | Fan motor cannot reach the requested speed (motor/board fault or obstruction at the fan) | Do a safe reset. If it continues, service is needed. |
| E162 | Indoor unit EEPROM (memory) error | Faulty/erased data in the main board memory | Service required |
| E201 | Indoor-outdoor unit count/pairing mismatch (multi/DVM) | Indoor unit count setting on the outdoor unit is wrong or a connection is missing | Service required |
| E202 | Indoor-outdoor communication error (no communication for 1 minute) | Power or communication cable connection problem | Check the outdoor unit fuse and do a safe reset. If it continues, service is needed. |
| E203 | Communication error between the outdoor unit main board and the inverter board | Outdoor unit board connection or board fault | Service required |
| E221 | Outdoor ambient temperature sensor error | Sensor open/short circuit or connection problem | Service required |
| E231 / E237 | Outdoor unit condenser (coil) temperature sensor error | Sensor open/short circuit or position/connection problem | Service required |
| E251 | Compressor discharge temperature sensor error | Sensor open/short circuit | Service required |
| E416 | Excessive rise in compressor discharge temperature | Gas shortage, flow problem or sensor problem | Service required |
| E422 | Electronic expansion valve (EEV) or service valve closed error | Closed service valve or EEV fault | Service required |
| E440 / E441 | Outdoor temperature is outside operating limits (E440 heating, E441 cooling blocked) | Outdoor air is not within the allowed range for the selected mode (in one service manual: above 30°C for heating, below -5°C for cooling; may vary by model) | Not a fault; the unit runs when the outdoor temperature returns to the suitable range. Check the mode setting. |
| E458 | Outdoor unit fan motor error | Fan motor fault or obstruction caught in the fan | From the outside, clear obstructions in front of the outdoor fan. If it continues, service is needed. |
| E461 | Compressor start-up error | Compressor connection or compressor fault | Service required |
| E462 | Total current (I-trip) / PFC overcurrent error | Supply problem, gas charge problem, outdoor fan not running | Clear the area around the outdoor unit and do a safe reset. If it continues, service is needed. |
| E464 | IPM (power module) overcurrent error | Gas charge, compressor connection, closed service valve, obstruction around the unit | Remove obstructions around the indoor and outdoor units. If it continues, service is needed. |
| E465 | Compressor overload / voltage limit (V-limit) error | Compressor connection or compressor problem | Service required |
| E466 | DC link voltage too low/high | Mains voltage or AC supply connection problem | Do a safe reset after the mains fluctuation has passed. If it continues, service is needed. |
| E467 | Compressor rotation error (compressor cable missing) | Compressor connection or compressor fault | Service required |
| E554 | Gas leak error | Refrigerant leak or shortage | Service required |
| E556 | Indoor and outdoor unit capacity mismatch | Incompatible model pairing | Service required |
Source: samsung.com · samsung.com · manualsdump.com
Toshiba fault codes
| Code | Meaning | Likely cause | What can you do? |
|---|---|---|---|
| E01 | Communication error between controller and indoor unit (detected on the controller side) | Controller cable, main (master) indoor unit switched off | Do a safe reset. If it continues, service is needed. |
| E03 | Indoor unit cannot receive a signal from the controller | Controller or communication adapter cable problem | Do a safe reset. If it continues, service is needed. |
| E04 | Indoor-outdoor communication circuit error (detected on the indoor unit side) | Interconnection cable fault, outdoor/indoor board fault, outdoor unit not running | Check the outdoor unit's fuse and do a safe reset. If it continues, service is needed. |
| E08 | Indoor unit address conflict | Wrong group/address setting | Service required |
| E10 | MCU communication error inside the indoor unit board | Indoor unit board or supply problem | Service required |
| F01 | Indoor unit heat exchanger sensor (TCJ, liquid) fault | Sensor open/short circuit or came off its position | Service required |
| F02 | Indoor unit heat exchanger sensor (TC/TC2) fault | Sensor open/short circuit or came off its position | Service required |
| F04 | Outdoor unit discharge sensor (TD) fault | Sensor open/short circuit | Service required |
| F06 | Outdoor unit heat exchanger sensor (TE/TS) fault | Sensor open/short circuit | Service required |
| F08 | Outdoor ambient temperature sensor (TO) fault | Sensor open/short circuit | Service required |
| F10 | Indoor unit return air (room) sensor (TA) fault | Sensor open/short circuit | Service required |
| H01 | Compressor fault / inverter compressor overcurrent | Compressor or inverter driver problem | Service required |
| H02 | Compressor lock (overcurrent right after starting) | Compressor mechanical lock or driver fault | Service required |
| H06 | Low pressure protection tripped | Gas shortage/leak or pressure sensor problem | Service required |
| L29 | Outdoor unit IPDU (inverter board) count/communication error | Outdoor unit board connection or board fault | Service required |
| L30 | Indoor unit external interlock input active | Stop signal from an external device (fire alarm, etc.) connected to the indoor unit board | Ask the person in charge about the status of the building automation/external devices. Service is required. |
| L31 | Phase detection protection (phase sequence/phase loss) – RAV series | Reverse phase or phase loss in the three-phase supply, outdoor board fault | If work has recently been done on the electrical installation, tell the electrician. Service is required. |
| P03 | Discharge temperature too high | Gas leak, expansion valve (PMV) fault, TD sensor problem | Service required |
| P04 | High pressure protection tripped | Overload in the cooling cycle, dirty/blocked outdoor heat exchanger, sensor problem | Clear the area around the outdoor unit and the air outlet. If it continues, service is needed. |
| P07 | Outdoor unit heat sink overheating | Insufficient outdoor unit ventilation or board problem | Clear the area around the outdoor unit and prevent hot air buildup. If it continues, service is needed. |
| P10 | Indoor unit overflow (float) error | Drain pump failure/blockage, float error | Switch the unit off; do not use it if water is dripping. Service is required. |
| P12 | Indoor unit DC fan motor error | Fan lock, driver overcurrent protection, board problem | Do a safe reset. If it continues, service is needed. |
| P19 | 4-way valve (heating/cooling changeover) error | 4-way valve fault or heat exchanger sensor problem | Service required |
| P22 | Outdoor unit DC fan motor error | Fan lock, position detection error, driver overcurrent | From the outside, clear obstructions in front of the outdoor fan. If it continues, service is needed. |
| P26 | Inverter overcurrent protection (G-Tr short circuit) | Short circuit in the compressor motor winding or IPDU wiring error | Service required |
| P29 | Compressor position detection circuit error | IPDU (inverter board) fault | Service required |
Source: toshiba-aircon.com.sg · klimaclassic.blob.core.windows.net · toshiba-aircon.co.uk
Carrier / Alarko Carrier fault codes
| Code | Meaning | Likely cause | What can you do? |
|---|---|---|---|
| E1 (indoor unit) | Communication error between the indoor and outdoor unit | Signal cable broken/reversed, interference, unshielded cable or board fault | Cut the unit's power and restore it after a few seconds. If it continues, service is needed. |
| E2 (indoor unit) | T1 (room temperature) sensor open/short circuit | Sensor or connector fault | Service required |
| E3 (indoor unit) | T2 (indoor coil midpoint) sensor open/short circuit | Sensor or connector fault | Service required |
| E4 (indoor unit) | T2B (indoor coil outlet) sensor open/short circuit | Sensor or connector fault | Service required |
| E7 (indoor unit) | Indoor unit EEPROM (memory) fault | EEPROM chip or indoor board fault | Do a safe reset. If it continues, service is needed. |
| E8 (indoor unit) | Indoor fan speed out of control (DC motor models) | Fan jam, bearing failure, motor or board problem | Do a safe reset. If it continues, service is needed. |
| EC (indoor unit) | Refrigerant leak protection | Gas leak (especially at valve connections), capillary tube blockage, T2 sensor coming off its position | Service required |
| Ed (indoor unit) | Outdoor unit fault (details on the outdoor unit display) | An error/protection is active on the outdoor unit or the outdoor unit is without power | Check that the outdoor unit's fuse is on. Service is required. |
| EE (indoor unit) | Water full (drain overflow) fault | Water level switch, drain pump failure or blocked discharge | Switch the unit off; do not use it if water is dripping. Service is required. |
| P0 (inverter floor-standing indoor unit) | Evaporator low temperature protection | Dirty filter, low airflow, low set temperature or gas problem | Clean the filter and clear the air inlet/outlet. If it continues, service is needed. |
| E0 (outdoor unit) | Outdoor unit EEPROM fault | Outdoor main board memory fault | Service required |
| E2 (outdoor unit) | Indoor-outdoor communication fault | Communication cable or board problem | Do a safe reset. If it continues, service is needed. |
| E3 (outdoor unit) | Communication fault between the IPM board and the outdoor main board | Signal cable between boards or board fault | Service required |
| E4 (outdoor unit) | T3 (condenser) or T4 (outdoor ambient) sensor open/short circuit | Sensor or cable fault | Service required |
| E5 (outdoor unit) | Compressor voltage protection | Abnormal mains voltage, connection or bridge diode/reactor problem | Restart the unit when the mains returns to normal. If it continues, service is needed. |
| E6 (outdoor unit) | PFC module protection (single-phase models with PFC board) | PFC module or connection fault | Service required |
| P0 (outdoor unit) | Compressor top (shell) temperature protection | Gas shortage, capillary blockage or protector failure | Service required |
| P1 (outdoor unit) | High pressure protection (model-specific) | High pressure switch/connection problem, very high ambient temperature, dirty condenser | Clear the area around the outdoor unit. If it continues, service is needed. |
| P2 (outdoor unit) | Low pressure protection (model-specific) | Gas shortage/leak or pressure switch problem | Service required |
| P3 (outdoor unit) | Compressor current protection | Overload, supply or compressor problem | Service required |
| P4 (outdoor unit) | Compressor discharge temperature protection | Gas shortage or flow problem | Service required |
| P5 (outdoor unit) | Condenser high temperature protection | Dirty condenser, insufficient outdoor unit ventilation, outdoor fan problem | Clear the area around the outdoor unit and remove items blocking the air outlet. If it continues, service is needed. |
| P6 (outdoor unit) | IPM module protection | Power module, compressor or supply problem | Service required |
| P7 (outdoor unit) | Evaporator high temperature protection (in heating) | Insufficient indoor unit airflow in heating (dirty filter) | Clean the indoor unit filter and clear the air inlet/outlet. If it continues, service is needed. |
Source: paperzz.com · alarko-carrier.com.tr
Arçelik / Beko fault codes
| Code | Meaning | Likely cause | What can you do? |
|---|---|---|---|
| F1–F5 | Fan speed level indicator (not a fault) | On models 18321 (Arçelik) / 31821 (Beko) produced in April 2017, the level is shown when the fan speed is changed | No action needed; this is normal. |
| CO | Auto Clean (smart cleaning) is running (not a fault) | The Auto Clean button was pressed on the remote; after the unit is switched off it dries/cleans itself for ~30 minutes | Wait, or turn the feature off by pressing the same button again. |
| CH01 | Indoor unit room temperature sensor error | Sensor or connection fault | Switch the breaker off and on after 3 min. If it continues, service is needed. |
| CH02 | Indoor unit inlet pipe sensor error | Sensor or connection fault | Switch the breaker off and on after 3 min. If it continues, service is needed. |
| CH03 | Wired remote controller error | Wired controller or connection problem | Service required |
| CH04 | Float switch error (optional, drain) | Drain/float problem | Service required |
| CH05 / CH53 | Communication error between the indoor and outdoor unit | Communication cable, outdoor unit without power or board problem | Switch the breaker off and on after 3 min. If it continues, service is needed. |
| CH06 | Indoor unit outlet pipe sensor error | Sensor or connection fault | Service required |
| CH09 | Indoor unit EEPROM error | Indoor unit board memory error | Service required |
| CH10 | Indoor unit BLDC fan motor impeller lock | Fan motor lock or motor fault | Switch the breaker off and on after 3 min. If it continues, service is needed. |
| CH21 | DC current (IPM) error | Inverter power module protection | Service required |
| CH23 | DC link low voltage error | Supply voltage or board problem | Switch the breaker off and on after 3 min. If it continues, service is needed. |
| CH26 | DC compressor position error | Compressor or driver circuit problem | Service required |
| CH29 | Compressor phase error / overcurrent error | Compressor or driver problem | Service required |
| CH32 | Compressor discharge line pipe sensor overheating error | Gas shortage or flow problem | Service required |
| CH34 | High pressure sensor – high pressure error | Dirty condenser, insufficient outdoor unit ventilation | Clear the area around the outdoor unit. If it continues, service is needed. |
| CH35 | Low pressure sensor – low pressure error | Gas shortage/leak | Service required |
| CH36 / CH38 | Refrigerant (gas) leak error | Gas leak or insufficient charge | Service required |
| CH44 | Outdoor air sensor error | Sensor or connection fault | Service required |
| CH51 | Capacity exceeded (wrong indoor/outdoor unit pairing) | Incompatible indoor/outdoor unit combination | Service required |
| CH61 | Condenser pipe temperature high error | Insufficient outdoor unit ventilation, dirty condenser | Clear the area around the outdoor unit and the air outlet. If it continues, service is needed. |
| CH62 | Main board heat sink sensor temperature high | Insufficient outdoor unit ventilation or board problem | Clear the area around the outdoor unit. If it continues, service is needed. |
| CH67 | Outdoor unit BLDC fan motor lock error | Obstruction in front of the outdoor fan or motor fault | From the outside, clear obstructions in front of the outdoor fan. If it continues, service is needed. |
| CH72 | 4-way valve position error | 4-way valve or control problem | Service required |
| CH93 | Indoor-outdoor communication error | Communication cable or outdoor unit supply problem | Switch the breaker off and on after 3 min. If it continues, service is needed. |
Source: arcelik.com.tr · arcelik.com.tr
Vestel fault codes
| Code | Meaning | Likely cause | What can you do? |
|---|---|---|---|
| SR 01 (formerly ER 01) | Indoor unit ambient (room) sensor open/short circuit | Sensor fault. The unit does not stop; it ignores the room sensor and keeps running as if at 24°C. | The unit keeps running but service is required. |
| ER 02 | Compressor cable not connected / software-compressor mismatch | Outdoor unit connection or board problem (outdoor LED: 25 blinks) | Service required |
| ER 03 | Indoor unit pipe sensor open/short circuit | Sensor fault | Service required |
| ER 04 | Indoor unit fan motor error | Fan jam, rubbing or motor/board fault | Do a safe reset. If it continues, service is needed. |
| ER 05 | Indoor unit setup (configuration data) not done/erased | Board parameter data missing | Service required |
| ER 06 | Indoor and outdoor unit communication error | Connection cable or board problem, outdoor unit without power (outdoor LED: 9 blinks) | Do a safe reset. If it continues, service is needed. |
| ER 07 | Refrigeration system error (gas low/empty) | Gas leak or insufficient charge (outdoor LED: 7 blinks) | Service required |
| SR 08 | Outdoor unit pipe sensor open/short circuit | Sensor fault (outdoor LED: 14 blinks) | Service required |
| ER 09 | Model mismatch between units | Incompatible indoor/outdoor unit pairing (outdoor LED: 22 blinks) | Service required |
| ER 10 | Electronic board heat sink sensor open/short circuit | Sensor/board fault (outdoor LED: 15 blinks) | Service required |
| ER 11 | Compressor start protection | Compressor or driver board problem (outdoor LED: 11 blinks) | Do a safe reset. If it continues, service is needed. |
| ER 13 | Compressor overcurrent error (during operation) | Overload, supply or compressor problem (outdoor LED: 13 blinks) | Clear the area around the outdoor unit. If it continues, service is needed. |
| ER 14 | Compressor overcurrent error (at initial start) | Compressor or driver problem | Service required |
| ER 15 | Outdoor unit ambient sensor open/short circuit | Sensor fault (outdoor LED: 16 blinks) | Service required |
| ER 16 | Compressor discharge sensor open/short circuit | Sensor fault (outdoor LED: 17 blinks) | Service required |
| HL | Low/high voltage protection at start-up (mains-related) | Mains voltage is outside limits (outdoor LED: 18 blinks) | The unit runs when the mains voltage returns to normal; if it repeats often, have the electrical installation checked. If it continues, service is needed. |
| ER 17 | High voltage error during operation (board/reactor-related) | Board or reactor fault | Service required |
| ER 18 | Outdoor unit setup not done/erased | Outdoor board parameter data missing | Service required |
| ER 19 | Wi-Fi module communication error | Communication problem between the Wi-Fi module and the board | Do a safe reset. If it continues, service is needed. |
| ER UE | UVC LED error | UV-C sterilization LED module fault | Service required |
| ER PS | Air quality sensor open/short circuit | Sensor fault | Service required |
| E1 (Platinum A / Air Plus A) | Magnetic field warning affecting the electronic board | Electromagnetic interference from nearby devices | Move strong electromagnetic sources away from the indoor unit and reset. If it continues, service is required. |
| E6 (Platinum A / Air Plus A) | Mains voltage too high/low fault | Mains voltage fluctuation | This warning code does not require service (a service call would be charged). Reset once the voltage returns to normal. |
| E7 (Platinum A / Air Plus A) | Electronic board memory has been erased | Board memory data loss | Service required |
| 88 | 3-minute protection after a power outage | Waiting period to protect the compressor after power returns | Wait 3 minutes; no service is needed. |
| FW | Filter cleaning warning | Time to clean the filters | Clean the filters, then reset the warning by holding the (+) and (−) buttons on the remote for 5 seconds. |
Source: static.vestel.com.tr · static.vestel.com.tr · scribd.com
No code matched your search. Send us the code and a photo of the unit label, and we will diagnose it.