VRF outdoor units installed side by side on a building roof

VRF / VRV system sales, maintenance and repair

To keep dozens of indoor units on a single outdoor unit running smoothly, we manage addressing, communication, refrigerant balance and compressor health together.

In shortVRF (Variable Refrigerant Flow) is a central air conditioning system in which a single outdoor unit serves many indoor units individually by varying the refrigerant flow. YOİ Mühendislik provides maintenance, fault code diagnostics, PCB repair, refrigerant leak detection and compressor replacement for VRF and VRV systems of all brands across Türkiye.
Free VRF System Maintenance Form (PDF)
A4 form with checklist, measurement table and signature fields.
Download PDFView the form

About VRF / VRV systems

VRF systems are preferred in buildings that need zoned heating and cooling, such as offices, hotels, hospitals, schools and shopping malls. Daikin calls this technology VRV; other manufacturers use names such as VRF or Multi V. Because the system consists of dozens of indoor units on a single piping network, a communication error or a small leak in one indoor unit can affect the entire system.

What we do

  • Fault code reading and diagnosis with service software
  • Indoor and outdoor unit PCB repair and replacement
  • Addressing, communication line and controller faults
  • Refrigerant leak detection, nitrogen test, evacuation and charging
  • Inverter compressor and fan motor replacement
  • Electronic expansion valve (EEV) service
  • Branch box and refnet joint checks
  • Heat recovery (3-pipe) system settings
YOİ Mühendislik technician measuring pressure with a manifold on a VRF outdoor unit
Pressure and superheat measurement on a VRF outdoor unit.

Common VRF faults

Symptom / alarmPossible causeWhat we do on site
Communication errorWiring, address conflict or PCB fault between indoor and outdoor unitsLine measurement, address scan, board test
High pressureDirty condenser, fan fault, overchargeFin washing, fan check, charge measurement
Low pressure / low refrigerantLeak, clogged filter, EEV faultLeak detection, nitrogen test, valve service
Compressor protectionPhase imbalance, inverter board, oil returnCurrent and winding measurement, PCB test
Indoor unit leaking waterCondensate pump, clogged drain pan, slopePump test, drain pan and line cleaning

Buildings we serve

Office and office towerHotelHospitalSchool and campusShopping mall and storePublic buildingResidence

We are headquartered in Etimesgut, Ankara. We provide VRF / VRV system service daily in Ankara, and on a project and contract basis across all 81 provinces of Türkiye, including İstanbul, İzmir, Bursa, Antalya, Konya, Kayseri, Eskişehir, Kocaeli, Adana, Gaziantep, Samsun and Trabzon. See our service areas.

Frequently asked questions

How many times a year should VRF system maintenance be done?

For commercial use, at least twice a year is recommended, before the summer and winter seasons. In heavily used hospitals and hotels, checks are done every three months.

Is it enough to tell you the VRF fault code over the phone?

Yes, the error code and equipment brand are usually enough for a preliminary diagnosis. The team arrives with the right part, making a first-visit fix more likely.

Do you maintain VRF systems of different brands?

Yes. We work with all brands, including Daikin VRV, LG Multi V, Mitsubishi, Toshiba, Samsung, Hitachi, Fujitsu, Midea and Gree.

How is a VRF refrigerant leak located?

The system is divided into sections and pressure-tested with nitrogen, the leak point is located with an electronic detector and bubble test, and after repair the system is evacuated and precisely recharged.

From 1 unit to 1,000 units, from a single provider.

Sales, installation, maintenance and repair for all brands and equipment. Nationwide across Türkiye.