Measuring pressures on a R454C refrigeration system

R454C refrigerant: properties, uses and alternatives

R454C has a GWP below 150 and was developed for commercial refrigeration and heat pumps.

In shortR454C has a GWP below 150 and was developed for commercial refrigeration and heat pumps. It is one of the next-generation replacements for R404A and R22.

R454C properties

CodeR454C
Chemical name / compositionBlend of R32 and R1234yf
R32 / R1234yf (21.5% / 78.5%)
FamilyHFO/HFC blend
GWP (AR4, 100 years)148
ODP0
Safety class (ISO 817 / ASHRAE 34)A2L: lower toxicity, mildly flammable
Boiling point (1 atm)−46.0 °C
Temperature glide7.8 K
Charge equal to 5 t CO₂e33.8 kg
StatusNext generation

Where is R454C used?

  • Commercial refrigeration and condensing units
  • Heat pumps
  • Cold rooms

Service and safety notes

  • Zeotropic blend, glide about 7.8 K: always charge in liquid phase; after a large leak, recover and recharge the full system. Use dew point for superheat and bubble point for subcooling.
  • Mildly flammable (A2L). Work away from ignition sources, use A2L-rated vacuum pumps, recovery units and leak detectors, and respect charge limits for the room size (EN 378).
  • Never charge a system with a refrigerant other than the one on its nameplate; retrofits need manufacturer approval and oil and component checks.
  • Charging, recovery and leak checks must be done and recorded by F-gas certified technicians.

R454C and regulations

Covered by Türkiye's Regulation on Fluorinated Greenhouse Gases (Official Gazette, 15 October 2024). HFC supply is being phased down with quotas, high-GWP gases are restricted earlier, leak-check intervals depend on the CO₂-equivalent charge, and handling requires certified technicians. With a GWP below 750 it is among the preferred next-generation options. Always check the current legal text for exact dates and scope.

Alternatives to R454C

  • R290: Hydrocarbon (natural), GWP 3, A3
  • R744: Natural refrigerant, GWP 1, A1
  • R448A: HFO/HFC blend, GWP 1,387, A1

Compare all refrigerants in our refrigerant guide.

Other refrigerants

Our base is in Ankara Etimesgut. We work daily in Ankara and on a project and contract basis across Türkiye. Türkçe sayfa.

Frequently asked questions

What is the GWP of R454C?

The 100-year global warming potential (AR4) of R454C is about 148.

Is R454C flammable?

A2L: lower toxicity, mildly flammable.

What can replace R454C?

Depending on the application: R290, R744, R448A. Conversions require manufacturer approval and oil and component checks.

Service for R454C systems

Site survey, measured diagnosis and a written quote. Based in Ankara, working across Türkiye.

Contact us

Get a quote, we reply the same day

Briefly describe your equipment and needs and one of our engineers will call you. One contact for breakdowns, maintenance, contracts and new equipment.

Authorized ServiceTSE Service Competence CertificateSince 2009

Quick quote form

The form is sent as a WhatsApp message.

For a detailed request, use our quote form.