R407F properties
| Code | R407F |
|---|---|
| Chemical name / composition | Blend of R32, R125 and R134a R32 / R125 / R134a (30% / 30% / 40%) |
| Family | HFC blend |
| GWP (AR4, 100 years) | 1,825 |
| ODP | 0 |
| Safety class (ISO 817 / ASHRAE 34) | A1: lower toxicity, non-flammable |
| Boiling point (1 atm) | −46.1 °C |
| Temperature glide | 6.4 K |
| Charge equal to 5 t CO₂e | 2.74 kg |
| Status | Being phased down |
Where is R407F used?
- Supermarket refrigeration
- Cold rooms
- R404A and R22 retrofits
Service and safety notes
- Zeotropic blend, glide about 6.4 K: always charge in liquid phase; after a large leak, recover and recharge the full system. Use dew point for superheat and bubble point for subcooling.
- Non-flammable and low toxicity (A1). A large leak in a closed room can still displace oxygen, so gas detection is recommended in small plant rooms.
- Never charge a system with a refrigerant other than the one on its nameplate; retrofits need manufacturer approval and oil and component checks.
- Charging, recovery and leak checks must be done and recorded by F-gas certified technicians.
R407F and regulations
Covered by Türkiye's Regulation on Fluorinated Greenhouse Gases (Official Gazette, 15 October 2024). HFC supply is being phased down with quotas, high-GWP gases are restricted earlier, leak-check intervals depend on the CO₂-equivalent charge, and handling requires certified technicians. Always check the current legal text for exact dates and scope.
Alternatives to R407F
- R448A: HFO/HFC blend, GWP 1,387, A1
- R449A: HFO/HFC blend, GWP 1,397, A1
- R744: Natural refrigerant, GWP 1, A1
Compare all refrigerants in our refrigerant guide.
Other refrigerants
Our base is in Ankara Etimesgut. We work daily in Ankara and on a project and contract basis across Türkiye. Türkçe sayfa.
Frequently asked questions
What is the GWP of R407F?
The 100-year global warming potential (AR4) of R407F is about 1,825.
Is R407F flammable?
A1: lower toxicity, non-flammable.
What can replace R407F?
Depending on the application: R448A, R449A, R744. Conversions require manufacturer approval and oil and component checks.