Measuring pressures on a R422D refrigeration system

R422D refrigerant: properties, uses and alternatives

R422D is a retrofit refrigerant mainly for R22 chillers and commercial refrigeration.

In shortR422D is a retrofit refrigerant mainly for R22 chillers and commercial refrigeration. It can be used without an oil change but has a high GWP.

R422D properties

CodeR422D
Chemical name / compositionBlend of R125, R134a and R600a
R125 / R134a / R600a (65.1% / 31.5% / 3.4%)
FamilyHFC blend
GWP (AR4, 100 years)2,729
ODP0
Safety class (ISO 817 / ASHRAE 34)A1: lower toxicity, non-flammable
Boiling point (1 atm)−43.2 °C
Temperature glide4.5 K
Charge equal to 5 t CO₂e1.83 kg
StatusBeing phased down

Where is R422D used?

  • Retrofit of R22 chillers
  • Retrofit of R22 commercial and industrial refrigeration

Service and safety notes

  • Zeotropic blend, glide about 4.5 K: always charge in liquid phase; after a large leak, recover and recharge the full system. Use dew point for superheat and bubble point for subcooling.
  • Non-flammable and low toxicity (A1). A large leak in a closed room can still displace oxygen, so gas detection is recommended in small plant rooms.
  • Never charge a system with a refrigerant other than the one on its nameplate; retrofits need manufacturer approval and oil and component checks.
  • Charging, recovery and leak checks must be done and recorded by F-gas certified technicians.

R422D and regulations

Covered by Türkiye's Regulation on Fluorinated Greenhouse Gases (Official Gazette, 15 October 2024). HFC supply is being phased down with quotas, high-GWP gases are restricted earlier, leak-check intervals depend on the CO₂-equivalent charge, and handling requires certified technicians. With a GWP above 2,500 it should not be chosen for new systems; existing systems should plan a conversion. Always check the current legal text for exact dates and scope.

Alternatives to R422D

  • R417A: HFC blend, GWP 2,346, A1
  • R407C: HFC blend, GWP 1,774, A1
  • R513A: HFO/HFC blend, GWP 631, A1

Compare all refrigerants in our refrigerant guide.

Other refrigerants

Our base is in Ankara Etimesgut. We work daily in Ankara and on a project and contract basis across Türkiye. Türkçe sayfa.

Frequently asked questions

What is the GWP of R422D?

The 100-year global warming potential (AR4) of R422D is about 2,729.

Is R422D flammable?

A1: lower toxicity, non-flammable.

What can replace R422D?

Depending on the application: R417A, R407C, R513A. Conversions require manufacturer approval and oil and component checks.

Service for R422D systems

Site survey, measured diagnosis and a written quote. Based in Ankara, working across Türkiye.

Contact us

Get a quote, we reply the same day

Briefly describe your equipment and needs and one of our engineers will call you. One contact for breakdowns, maintenance, contracts and new equipment.

Authorized ServiceTSE Service Competence CertificateSince 2009

Quick quote form

The form is sent as a WhatsApp message.

For a detailed request, use our quote form.