Authorized Service · TSE Service Competence Certified · ISO 9001 · OHSAuthorized Service · Serving all 81 provinces of TürkiyeServing all of Türkiye0312 261 07 24info@yoimuhendislik.com.tr
Measuring pressures on a R449A refrigeration system

R449A refrigerant: properties, uses and alternatives

R449A is a non-flammable alternative for R404A, R507A and R22 commercial refrigeration, with properties very close to R448A..

In shortR449A is a non-flammable alternative for R404A, R507A and R22 commercial refrigeration, with properties very close to R448A.

R449A properties

CodeR449A
Chemical name / compositionBlend of R32, R125, R1234yf and R134a
R32 / R125 / R1234yf / R134a (24.3% / 24.7% / 25.3% / 25.7%)
FamilyHFO/HFC blend
GWP (AR4, 100 years)1,397
ODP0
Safety class (ISO 817 / ASHRAE 34)A1: lower toxicity, non-flammable
Boiling point (1 atm)−46.0 °C
Temperature glide4.0 K
Charge equal to 5 t CO₂e3.58 kg
StatusIn common use

Where is R449A used?

  • Supermarket and commercial refrigeration
  • Cold rooms
  • R404A / R507A / R22 retrofits

Service and safety notes

  • Zeotropic blend, glide about 4.0 K: always charge in liquid phase; after a large leak, recover and recharge the full system. Use dew point for superheat and bubble point for subcooling.
  • Non-flammable and low toxicity (A1). A large leak in a closed room can still displace oxygen, so gas detection is recommended in small plant rooms.
  • Never charge a system with a refrigerant other than the one on its nameplate; retrofits need manufacturer approval and oil and component checks.
  • Charging, recovery and leak checks must be done and recorded by F-gas certified technicians.

R449A and regulations

Covered by Türkiye's Regulation on Fluorinated Greenhouse Gases (Official Gazette, 15 October 2024). HFC supply is being phased down with quotas, high-GWP gases are restricted earlier, leak-check intervals depend on the CO₂-equivalent charge, and handling requires certified technicians. Always check the current legal text for exact dates and scope.

Alternatives to R449A

  • R448A: HFO/HFC blend, GWP 1,387, A1
  • R744: Natural refrigerant, GWP 1, A1
  • R290: Hydrocarbon (natural), GWP 3, A3

Compare all refrigerants in our refrigerant guide.

Other refrigerants

Our base is in Ankara Etimesgut. We work daily in Ankara and on a project and contract basis across Türkiye. Türkçe sayfa.

Frequently asked questions

What is the GWP of R449A?

The 100-year global warming potential (AR4) of R449A is about 1,397.

Is R449A flammable?

A1: lower toxicity, non-flammable.

What can replace R449A?

Depending on the application: R448A, R744, R290. Conversions require manufacturer approval and oil and component checks.

Service for R449A systems

Site survey, measured diagnosis and a written quote. Based in Ankara, working across Türkiye.