How the system works
- The CHP unit generates electricity.
- Heat recovery from jacket water, oil cooler and exhaust produces hot water or steam.
- In winter the heat is used for space or process heating.
- In summer it drives an absorption chiller to produce chilled water.
- Heat is rejected by a dry cooler or cooling tower.
Absorption chiller maintenance
- Vacuum level and purge system checks
- Solution analysis: concentration, inhibitor, corrosion indicators
- Crystallisation risk monitoring
- Heat exchanger tubes, solution and refrigerant pumps, control valves
- Cooling water circuit and water treatment
Maintenance of the CHP engine and generator is done by its manufacturer or authorised service; we work on heat recovery, absorption chillers and the chilled and cooling water circuits.
Maintenance, repair, installation and projects
- Scheduled maintenance: condenser and evaporator cleaning, compressor and oil checks, pressure and temperature measurements, safety device tests, measured report.
- Fault diagnosis and repair: not reaching set temperature, slow pull-down, high/low pressure alarms, compressor failure, leaks, control and sensor faults.
- Installation and projects: load calculation, system and refrigerant selection, compressor and heat exchanger selection, installation, commissioning and documentation.
- Retrofit and modernisation: conversion to new refrigerants, compressor overhaul, control upgrades, energy efficiency improvements.
We work brand-independent; refrigerant handling is done by F-gas certified technicians.
Our base is in Ankara Etimesgut. We work daily in Ankara and on a project and contract basis across Türkiye. Türkçe sayfa.
Frequently asked questions
Which brands do you service?
We work brand-independent, using the nameplate, circuit diagram and fault records for diagnosis.
Do you work outside Ankara?
Yes. We are based in Ankara and work across Türkiye on a project, contract and scheduled service basis.
Do you also design and install new systems?
Yes. We calculate loads, select the system and refrigerant, install and commission.